feat(ventcool): Add a schema for VentilationFan
Browse files Browse the repository at this point in the history
  • Loading branch information
chriswmackey authored and Chris Mackey committed Dec 5, 2023
1 parent 6094e87 commit fcfa520
Show file tree
Hide file tree
Showing 2 changed files with 87 additions and 1 deletion.
14 changes: 13 additions & 1 deletion honeybee_schema/energy/properties.py
Original file line number Diff line number Diff line change
Expand Up @@ -19,7 +19,7 @@
GasEquipmentAbridged, ServiceHotWaterAbridged, InfiltrationAbridged, \
VentilationAbridged, SetpointAbridged, ProcessAbridged
from .daylight import DaylightingControl
from .ventcool import VentilationControlAbridged, VentilationOpening, \
from .ventcool import VentilationControlAbridged, VentilationFan, VentilationOpening, \
VentilationSimulationControl, AFNCrack
from .internalmass import InternalMassAbridged
from .schedule import ScheduleTypeLimit, ScheduleRulesetAbridged, \
Expand Down Expand Up @@ -245,6 +245,18 @@ class RoomEnergyPropertiesAbridged(NoExtraBaseModel):
'of windows. If None, the windows will never open.'
)

fans: List[VentilationFan] = Field(
default=None,
description='An optional list of VentilationFan objects for fans within the '
'room. Note that these fans are not connected to the heating or cooling system '
'and are meant to represent the intentional circulation of unconditioned '
'outdoor air for the purposes of keeping a space cooler, drier or free '
'of indoor pollutants (as in the case of kitchen or bathroom exhaust fans). '
'For the specification of mechanical ventilation of conditioned outdoor air, '
'the Room.ventilation property should be used and the Room should be '
'given a HVAC that can meet this specification.'
)

internal_masses: List[InternalMassAbridged] = Field(
default=None,
description='An optional list of of InternalMass objects for thermal mass '
Expand Down
74 changes: 74 additions & 0 deletions honeybee_schema/energy/ventcool.py
Original file line number Diff line number Diff line change
Expand Up @@ -2,6 +2,7 @@
from pydantic import Field, constr

from .._base import NoExtraBaseModel
from ._base import EnergyBaseModel
from enum import Enum


Expand Down Expand Up @@ -66,6 +67,79 @@ class VentilationControlAbridged(NoExtraBaseModel):
)


class VentilationType(str, Enum):
exhaust = 'Exhaust'
intake = 'Intake'
balanced = 'Balanced'


class VentilationFan(EnergyBaseModel):

type: constr(regex='^VentilationFan$') = 'VentilationFan'

flow_rate: float = Field(
...,
gt=0,
description='A number for the flow rate of the fan in m3/s.'
)

ventilation_type: VentilationType = Field(
default=VentilationType.balanced,
description='Text to indicate the type of type of ventilation. Choose '
'from the options below. For either Exhaust or Intake, values for '
'fan pressure and efficiency define the fan electric consumption. For Exhaust '
'ventilation, the conditions of the air entering the space are assumed '
'to be equivalent to outside air conditions. For Intake and Balanced '
'ventilation, an appropriate amount of fan heat is added to the '
'entering air stream. For Balanced ventilation, both an intake fan '
'and an exhaust fan are assumed to co-exist, both having the same '
'flow rate and power consumption (using the entered values for fan '
'pressure rise and fan total efficiency). Thus, the fan electric '
'consumption for Balanced ventilation is twice that for the Exhaust or '
'Intake ventilation types which employ only a single fan.'
)

pressure_rise: float = Field(
...,
gt=0,
description='A number for the the pressure rise across the fan in Pascals '
'(N/m2). This is often a function of the fan speed and the conditions in '
'which the fan is operating since having the fan blow air through filters '
'or narrow ducts will increase the pressure rise that is needed to '
'deliver the input flow rate. The pressure rise plays an important role in '
'determining the amount of energy consumed by the fan. Smaller fans like '
'a 0.05 m3/s desk fan tend to have lower pressure rises around 60 Pa. '
'Larger fans, such as a 6 m3/s fan used for ventilating a large room tend '
'to have higher pressure rises around 400 Pa. The highest pressure rises '
'are typically for large fans blowing air through ducts and filters, which '
'can have pressure rises as high as 1000 Pa.'
)

efficiency: float = Field(
...,
ge=0,
le=1,
description='A number between 0 and 1 for the overall efficiency of the fan. '
'Specifically, this is the ratio of the power delivered to the fluid '
'to the electrical input power. It is the product of the fan motor '
'efficiency and the fan impeller efficiency. Fans that have a higher blade '
'diameter and operate at lower speeds with smaller pressure rises for '
'their size tend to have higher efficiencies. Because motor efficiencies '
'are typically between 0.8 and 0.9, the best overall fan efficiencies '
'tend to be around 0.7 with most typical fan efficiencies between 0.5 and '
'0.7. The lowest efficiencies often happen for small fans in situations '
'with high pressure rises for their size, which can result in efficiencies '
'as low as 0.15.'
)

control: VentilationControlAbridged = Field(
default=None,
description='A VentilationControl object that dictates the conditions under '
'which the fan is turned on. If None, a default VentilationControl will '
'be generated, which will keep the fan on all of the time.'
)


class VentilationOpening(NoExtraBaseModel):

type: constr(regex='^VentilationOpening$') = 'VentilationOpening'
Expand Down