Created on Tue Apr 21 10:54:52 2020
@author: cghiaus
test winter_VaHum.py
https://www.spyder-ide.org/blog/introducing-unittest-plugin/
"""
# from winter_VaHum import ModelAllOutAir, AllOutAirCAV, ModelRecAir
import winter_VaHum as vh
import numpy as np
def test_vhModelAllOutAir():
"""
--o->HC--0->VH--1->TZ--2-->
/ / || |
| | BL |
| | |
| |<----Kw--|-w2
|<------------Kt--|-t2
"""
# Input data
m, tS = 4.84, 30 # supply air mass flow kg/s; temp. °C
tIsp, phiIsp = 18, 0.50 # indoor set point temp. °C; RH -
tO, phiO = -1, 1 # outdoor temp. °C; RH -
Qsa, Qla = 0, 0 # aux. sens. ; latent loads W
mi, UA = 2.12, 935.83 # bldg. inflitr. k/s ; conductivity W/K
# Expected results
y = np.array([30, 3.5076e-3, # point 0 (t, w)
30, 7.670e-3, # point 1 (t, w)
18, 6.4025e-3, # point 2 (t, w)
150020.8, 50290.27, # QsHC, QlVH
-58060.78, -15318.30]) # QsTZ, QlTZ
np.testing.assert_almost_equal(
vh.ModelAllOutAir(m, tS, tIsp, phiIsp, tO, phiO, Qsa, Qla, mi, UA),
y, 1)
def test_vhAllOutAirCAV():
"""
--o->HC--0->VH--1->TZ--2-->
/ / || |
| | BL |
| | |
| |<----Kw--|-w2
|<------------Kt--|-t2
"""
# Expected results
y = np.array([29.77, 3.5076e-3, # point 0 (t0, w0)
29.77, 7.6465e-3, # point 1 (t1, w1)
18, 6.4025e-3, # point 2 (t2, w2)
151795.37, 50965.12, # QsHC, QlVH
-58060.78, -15318.30]) # QsTZ, QlTZ
np.testing.assert_almost_equal(
vh.AllOutAirCAV(tS=30, tIsp=18, phiIsp=0.5, tO=-1, phiO=1,
Qsa=0, Qla=0, mi=2.12, UA=935.83),
y, 2)
def test_vhModelRecAir():
"""
<-3--|<-------------------------|
| |
-o->MX--0->HC--1->VH--2->TZ--3-->
/ / || |
| | BL |
| | |
| |<----Kw--|-w3
|<------------Kt--|-t3
"""
# Input data
m = 4.84 # supply air mass flow kg/s
alpha = 1 # 100 % outdoor air
tS = 30 # supply air °C
tIsp, phiIsp = 18, 0.50 # indoor set point temp. °C; RH -
tO, phiO = -1, 1 # outdoor temp. °C; RH -
Qsa, Qla = 0, 0 # aux. sens. ; latent loads W
mi, UA = 2.12, 935.83 # bldg. inflitr. k/s ; conductivity W/K
# Expected results
y = np.array([-1, 3.5076e-3, # point 0 (t0, w0)
29.996, 3.5076e-3, # point 1 (t1, w1)
29.996, 7.6611e-3, # point 2 (t2, w2)
18, 6.3960e-3, # point 3 (t3, w3)
150020.65, 50176.49, # QsHC, QlVH
-58060.72, -15283.64]) # QsTZ, QlTZ
np.testing.assert_almost_equal(
vh.ModelRecAir(m, alpha, tS, tIsp, phiIsp, tO, phiO, Qsa, Qla, mi, UA),
y, 2)